Published in

Trans Tech Publications, Key Engineering Materials, (730), p. 81-86

DOI: 10.4028/www.scientific.net/kem.730.81

Links

Tools

Export citation

Search in Google Scholar

Corrosion Mechanism Analysis of a 20<sup>#</sup> Carbon Steel Lightning Rod on a Substation

Journal article published in 2017 by Yu Tong Zhou, Jiong Geng Wang, Hong Ye Zheng, Jie Zi Hu, Jie Zhang, Jia Yuan Hu
This paper was not found in any repository, but could be made available legally by the author.
This paper was not found in any repository, but could be made available legally by the author.

Full text: Unavailable

Red circle
Preprint: archiving forbidden
Red circle
Postprint: archiving forbidden
Green circle
Published version: archiving allowed
Data provided by SHERPA/RoMEO

Abstract

A lightning rod on a coastal substation cracked, so the related equipment is forced to be shut down. Optical microscope, spectrometer, SEM, EDS and ion chromatograph were adopted to analyze the corrosion mechanism. Results show that the lightning rod is corroded severely. The material of this lightning rod is 20# carbon steel. The corroded part and the uncorroded part are divided into two layers. Nodulizing of pearlites is evident in the microstructure of corroded area. Both of EDS and ion chromatograph detect high concentration of chloride ion and sulfate ion from the corrosion products. In this sense, corrosion is probably induced by coastal-industrial atmosphere and rainwater pollution. Besides, improper structure of the lightning rod is also a factor to cause the corrosion.