Published in

Springer (part of Springer Nature), Bioprocess and Biosystems Engineering, 5(36), p. 627-634

DOI: 10.1007/s00449-012-0831-0

Links

Tools

Export citation

Search in Google Scholar

Continuous fill intermittent decant type sequencing batch reactor application to upgrade the UASB treated sewage

This paper is available in a repository.
This paper is available in a repository.

Full text: Download

Green circle
Preprint: archiving allowed
Green circle
Postprint: archiving allowed
Red circle
Published version: archiving forbidden
Data provided by SHERPA/RoMEO

Abstract

The performance of continuous flow intermittent decant type sequencing batch (CFID) reactor treating the effluent of an UASB reactor treating domestic wastewater and operated at 8 h hydraulic retention time (HRT) was investigated. The CFID was operated at three different HRTs (22, 8 and 6 h) and three different dissolved oxygen (DO) patterns (<0.5, 2.5-3.5 and 3.5-4.5 mg/L). The highest effluent quality was observed at the 8 h HRT and 2.5-3.5 mg/L DO concentration. At this operational condition, the average BOD, TSS, ammonia nitrogen and fecal coliform removal efficiencies were 83, 90, 74 and 99 %, respectively. The CFID is a promising post-treatment option for existing UASB systems, with a final effluent quality that comply with receiving water and effluent reuse criteria.