Published in

Trans Tech Publications, Applied Mechanics and Materials, (738-739), p. 11-14, 2015

DOI: 10.4028/www.scientific.net/amm.738-739.11

Links

Tools

Export citation

Search in Google Scholar

Fiber Bragg Grating Hydrogen Sensor Applied for Partial Discharge Detection in Transformer Oil

Journal article published in 2015 by Ying Ting Luo, Hong Bin Wang, Wen Jun Zhu, Zhen Wu, Hong Tu Song, Xiong Li
This paper was not found in any repository, but could be made available legally by the author.
This paper was not found in any repository, but could be made available legally by the author.

Full text: Unavailable

Red circle
Preprint: archiving forbidden
Red circle
Postprint: archiving forbidden
Green circle
Published version: archiving allowed
Data provided by SHERPA/RoMEO

Abstract

Most optical hydrogen sensors are based on light intensity measurement and light intensity detection is vulnerable to the light source output and the optical fiber arrangement. To overcome the shortcomings, an optical fiber based sensor based on fiber Bragg grating (FBG) technique which is capable to measure the concentration of hydrogen dissolved is described in this paper. To examine the availability of monitoring initial hydrogen generation, a needle-to-plate partial discharge (PD) model was setup in the lab. The results between wavelength shifts of optical hydrogen sensor well agreed with conventional dissolved gas analysis (DGA), proving a potential utilization in the detection of dissolved hydrogen in power transformer.