Published in

Institute of Electrical and Electronics Engineers, IEEE Journal of Emerging and Selected Topics in Power Electronics, 1(4), p. 221-233, 2016

DOI: 10.1109/jestpe.2015.2504845

Links

Tools

Export citation

Search in Google Scholar

Current Harmonics from Single-Phase Grid-Connected Inverters - Examination and Suppression

Journal article published in 2016 by Yongheng Yang ORCID, Keliang Zhou, Frede Blaabjerg
This paper is available in a repository.
This paper is available in a repository.

Full text: Download

Green circle
Preprint: archiving allowed
Green circle
Postprint: archiving allowed
Red circle
Published version: archiving forbidden
Data provided by SHERPA/RoMEO

Abstract

Environmental conditions and operational modes may significantly impact the distortion level of the injected current from single-phase grid-connected inverter systems, such as photovoltaic (PV) inverters, which may operate in cloudy days with a maximum power point tracking, in a non-unity power factor, or in the low voltage ride through mode with reactive current injection. In this paper, the mechanism of the harmonic current injection from grid-connected single-phase inverter systems is thus explored, and the analysis is conducted on single-phase PV systems. In particular, the analysis is focused on the impacts of the power factor and the feed-in grid current level on the quality of the feed-in grid current from single-phase inverters. As a consequence, an internal model principle based high performance current control solution is tailor-made and developed for single-phase grid-connected systems to produce high quality currents in different operation conditions, where a design procedure is also provided. The developed current controller in this paper can achieve a minimum steady-state error while maintaining a relatively fast transient response, and also being feasible in other single-phase applications as a promising harmonic mitigation solution. Experiments on single-phase grid-connected systems have verified the correctness of the relevant analysis and also the effectiveness of the tailor-made control solution in terms of good harmonic mitigation.